Rolla Transformer Enclosures

Rolla have been supplying transformer enclosures for many years, mostly as part of a package sub-station, but also some stand alone versions. Typically each enclosure will house a cast resin transformer with 11kV primary and 400V secondary, in ratings from 500kVA to 3.5MVA.

Each enclosure is test assembled in our works before it is painted.

Tx Assembly in progress

Tx test assembly

Enclosures have an open floor, and assume that the transformer will sit on a solid base. We provide floor channels to spread the transformer load, and provide a guide to location.

tall tax enclosure

They come in all shapes and sizes to suit the particular transformer and the associated switchboard. We also supply a complete busbar system to fit in the top of each enclosure, with bars arranged to connect directly to the adjacent incomer section.

large lv connections

installed transformer

The overhead busbars use our own type tested arrangement (Rolla KATTA® system).

transformer lv connections

Connections on the LV side are through flexible links to provide adjustment and reduce vibration.

flexi links to transformer

We also provide channels for the floor, to spread the load of the wheels (transformers usually weigh several tonnes).

tx base channels

large view installed tx

As all the busbars are pre-manufactured, site assembly is usually quick and easy.

HV cables can come from above or below.

hc cables from below

hv connections

We can punch for an HV flange, to fit an external HV cable box if required.

HV Flange

The kit of parts is supplied on a pallet, with separate boxes for the copper busbars and loose fixings, bolts etc., ready for site assembly. In most cases the enclosure and the transformer are fitted on site at the same time, by the electrical contractor, who will also connect all the site wiring and carry out testing and commissioning.

site assembly

Cardiff Bay completed transformer

Hinged doors provide access for maintenance, tap changing etc. Colour will usually be to match the switchboard to customer's requirements.

transformer hoods

A key part of the design of these enclosures is the ventilation - air must be allowed in and out in order to keep the transformer cool. We use the transformer manufacturers data for the watts losses, whether AN or AF rated, and always allow spare capacity.

Most enclosures use simple coarse mesh (IP2X), as this has the best air transfer performance, but some sites use special non-vision transfer grilles.

non-vision grilles

Grille sizes calculated to suit ventilation requirements.

enclosure with non vision grilles

non vision air inlet grilles

Removable enclosure sections, including the base, allow the transformer to be withdrawn and replaced, without complete disassembly. This will depend on the site access requirements, floor loading etc.

The air can enter through the non-vision grilles easily, but the design means nothing can be poked directly into the enclosure, thus increasing safety. These type of grilles are often seen in air conditioning applications.

We always allow a large safety margin between the live connections and the sides of the enclosure, which also means the enclosure is easy to work in during the assembly phase.

In some cases the hot air is collected from above and ducted away, to prevent the building itself being overheated.

Incoming ACB sections have their busbars arranged to complement the transformer enclosure.

large ACB incomer bottom bars

package sub switchboard

Close coupling of the transformer to the switchboard means that the installation is compact and often simplifies the protection requirements. We are often required to provide CT links for class X CT's (Restricted Earth Fault) together with associated neutral to earth link within the main incomer section. Other protection and metering CT links are also provided as standard, to suit the requirements of each project.

site access doors

External doors will often be fitted with access interlocks (eg Fortress, Castell) which prevent access until the HV circuit has been isolated.

fortress interlock

We are familiar with many different transformer manufacturers products eg SGB, Zucchini, France Transfo, Ocrev etc.

SGB transformer

This is a typical SGB transformer in the stores before being sent to site, with axial blowers (fans) at low level. Many transformers are sent direct to site due to their size, but some customers prefer to fully works assemble and test.

Stay Updated with our Latest News

12
Oct
Major UK water infrastructure project

Rolla is proud to have been involved with a major UK water infrastructure project, the lar.....

Read More
07
Apr
Review of 2020

Over the last 12 months Rolla has continued to manufacture and deliver hundreds of project.....

Read More
06
Nov
Why low-voltage assemblies must comply with BS EN 61439

This recent article published by BEAMA in the Panel Building & System Integration (PBS.....

Read More
27
Mar
2019 Update

Rolla is now on Linkedin here https://www.linkedin.com/company/rolla-ltd/ Check it out an.....

Read More
17
Jan
Roundup of 2018 and early 2019

Variable speed drives have been very popular recently, usually the ultra low harmonic vers.....

Read More
05
Sep
2018 Update

As well as the usual boards we supply to the UK water industry, this year we have also bee.....

Read More